TR-Series
Industrial Refrigerant Gas Detector Transmitters
- Selectable Analogue Output (4-20mA, 0-10V)
- Connectivity to MPU or SPU monitoring unit
- Integrate with any PLC or gas detection controller accepting analogue signals
- -40°C- +50°C operating range (exc. TR-EC)
- Maintenance calibration gas & TR calibration kit
- Power supply 12-30V DC
TR-Series gas detector transmitters are robustly designed for use in harsh environments, offering simply reliable gas detection for industrial refrigerant applications.
There are a number of variants in the TR-xx platform to meet application-specific needs, all sharing a common set of
features.
These include:
• Selectable analogue output (4-20mA, 0-10V)
• Connectivity to MPU or SPU monitoring unit
• Integrate with any PLC or gas detection controller accepting analogue signals
• -40°C - + 50°C operating range (exc. TR-EC)
• Maintenance calibration gas & TR calibration kit
• Power supply 12-30V DC
TR-Series refrigerant gas detector transmitters can be delivered in several versions depending on the application and gas used.
The following options are available:
Model Types
TR-IR
CO2 detection using infrared sensor
IP67 enclosure
TR-SC
HFC / HFO / NH3 / R290 / flammable gas / VOC detection using semiconductor sensor
IP54 enclosure
TR-SCK
HFC / HFO / NH3 / R290 / flammable gas detection using semiconductor sensor
IP54 enclosure
Remote sensor, 1.5m cable
Ventilation ducts installation (plastic tube with the sensor
mounted with a rubber sleeve
directly in the channel)
TR-SCR
HFC / HFO / NH3 detector using semiconductor sensor
IP54 enclosure
Remote sensor, 1.5m cable
Vent lines from pressure relief valve installation
Pipe fitting in brass ½ ” Flare
TR-EC
NH3 / CO / NO2 detector using electrochemical sensor
IP67 enclosure
NH3: -30°C - + 50°C operating range
CO / NO2: -10°C - + 40°C operating range
TECHNICAL DATA
TR-EC-CO / TR-EC-NO2
TR-EC-CO | TR-EC-NO2 | |
Gas type: | Carbon monoxide (CO) | Nitrogen dioxide (NO2) |
Material: | Polycarbonate | Polycarbonate |
Method: | Electrochemical | Electrochemical |
Range: | 0-300 ppm | 0-20 ppm |
Lifetime sensor: | ~ 6 year | ~ 2 year |
Calibration interval: | Automatic zero adjustment, calibration span once a year. | Automatic zero adjustment, calibration span once a year. |
Power consumption: | 20mA | 20mA |
Power supply: | 12..28V DC | 12..28V DC |
Output: | 4..20mA / 0..10V DC linear | 4..20mA / 0..10V DC linear |
Ambient temp: | -10ºC..+40ºC | -10ºC..+40ºC |
Ambient humidity: | 0..90% RH | 0..90% RH |
Enclosure: | IP56 | IP56 |
Dimensions: | 80 x 82 x 86 mm | 80 x 82 x 86 mm |
Weight: | 190g | 190g |
Approvals: | CE, TÜV approved according to VDI | CE, TÜV approved according to VDI |
TR-EC-NH3
Gas type: | Ammonia (NH3) |
Material: | Polycarbonate |
Method: | Electrochemical |
Range: | 0-100 ppm / 0-1000 ppm / 0-5000 ppm / B1020-10000 ppm |
Lifetime sensor: | ~ 2-3 year |
Calibration interval: | > once a year. B101 |
Max (RL): | 250 ohm (input impedance) |
Power consumption: | 20mA |
Power supply: | 12..36V DC |
Output: | 4..20mA linear |
Ambient temp: | -30ºC..+50ºC |
Ambient humidity: | 15..90% RH |
Enclosure: | IP56 |
Dimensions: | 80 x 82 x 60 mm |
Weight: | 180g |
Approvals: | CE, EMC |
TR-SC-..
Sensor type: | Semiconductor |
Response time (T90): | <10 seconds |
Output signal: | 4..20mA (max 500 ohm) / 0..10V DC |
Calibration: | “zero / span” ≥ once per year |
Lifetime sensor: | >5 years (replacement recommended every 5th year or when unit can not be recalibrated) |
Power supply: | 12..30V DC |
Housing: | PC polycarbonate (IP54) |
Cable gland: | 1 x M16 |
TR-SC, Splash Proof (IP54) | |
Range / Gas | TR-SC-HCFC-4000: 0-4000ppm / HCFC (R22) |
TR-SC-HFC(A)-4000: 0-4000ppm / HFC (R404a, R407a, R410a, R507) | |
TR-SC-HFC(B)-4000:B144 0-4000ppm / (R134) | |
TR-SC-NH3-1000: 0-1000ppm / Ammonia | |
TR-SC-NH3-4000: 0-4000ppm / Ammonia | |
TR-SC-HC:B147 0-50% LEL / Hydrocarbon | |
TR-SC-H2:141:141 0-50% LEL / Hydrogen | |
Housing: | Polycarbonate / ABS |
Operating temperature: | -40ºC..+50ºC |
Operating humidity: | 10-90 % Rh (non condensing) |
Dimensions: | 130x82x56 mm |
TR-SCK, Duct Mounting | |
Range / Gas | TR-SCK-HCFC-4000: 0-4000ppm / HCFC (R22) |
TR-SCK-HFC(A)-4000 0-4000ppm / HFC (R404a, R407a, R410a, R507) | |
TR-SCK-HFC(B)-4000 0-4000ppm / (R134) | |
TR-SCK-NH3-1000 0-1000ppm / Ammonia | |
TR-SCK-NH3-4000 0-4000ppm / Ammonia | |
TR-SCK-HC 0-50% LEL / Hydrocarbon | |
TR-SCK-H2 0-50% LEL / Hydrogen | |
Transmitter Housing | 80 x 82 x 56 mm (IP54) |
Duct Tube | Plastic, L 350mm (PVC) |
Operating Temperature: | 0ºC..+50ºC |
Operating humidity: | 10-90 % Rh (non condensing) |
TR-SCR, For Vent Lines (Blow off pipes) | |
Range / Gas: | TR-SCR-HFC(B)-4000: 0-4000ppm / HFC (R134) |
TR-SCR-NH3-4000 0-4000ppm / Ammonia | |
Transmitter Housing | 80 x 82 x 56 mm (IP54) |
Pipe Connection: | 70x25 mm HFC - brass ½”-flare NH3 - steel R½” |
Operating Temperature: | 0ºC..+50ºC |
Operating humidity: | 10-90 % Rh (non condensing) |
TR-IR
TR-IR-CO2, Splash Proof (IP67) | |
Housing: | PC polycarbonate (IP67) |
Power Supply: | 12..30V DC |
Power consumption: | 2,5W |
Sensor type: | NDIR |
Response time (T90): | <10 seconds |
Output signal: | 4..20mA (min 250..max 500 ohm) / 0..10V DC |
Calibration: | Automatic Baseline Correction |
Control/Check: | The detector should be tested at least once per year |
Sensor Lifetime: | >15 year (replacement recommended every 10th year or when the unit no longer indicates any gas) |
Operating temperature: | -40ºC..50ºC |
Operating humidity: | 10-90 % Rh (non-condensing) |
Cable gland: | 1 x M16 |
Dimensions (LxHxD) | 80 x 82 x 56 mm |
Range / Gas: | TR-IR-CO2: 0-10000ppm Carbon Dioxide |
TR-IR-CO2: 0-20000/30000ppm Carbon Dioxide |
Coming soon...
Order Code | Model | Details | PG |
TR-IR | CO₂ |
| |
39-4312 | TR-IR-CO2-10000 | 0-10000 ppm, max 2,5 W | A |
39-4314 | TR-IR-CO2-30000 | 0-30000 ppm, max 2,5 W | A |
TR-SC detectors | HFC / HFO / NH₃ / R290 / flammable gas | ||
39-4120-A | TR-SC-HFC(A)-4000 | 0..4000 ppm HFC (standard R404a / R507) | A |
39-4120-B | TR-SC-HFC(B)-4000 | 0..4000 ppm HFC (standard R134a) | A |
39-4152 | TR-SC-NH3-4000 | 0..4000 ppm Ammonia, max 2 W | A |
39-4153 | TR-SC-NH3-10000 | 0..10000 ppm Ammonia, max 2 W | A |
39-4130 | TR-SC-HC | 0-50% LEL, General for Hydrocarbons (HC) | A |
39-4170 | TR-SC-H2 | 0-50% LEL, Hydrogen (H2) | A |
TR-SCK detectors | HFC / HFO / NH₃/ R290 / flammable gas | For ventilation ducts | |
39-8120-A | TR-SCK-HFC(A)-4000 | 0..4000 ppm HFC (standard R404a / R507) | A |
39-8120-B | TR-SCK-HFC(B)-4000 | 0..4000 ppm HFC (standard R134a) | A |
39-8152 | TR-SCK-NH3-4000 | 0..4000 ppm Ammonia, max 2 W | A |
39-8130 | TR-SCK-HC | 0-50% LEL, General for Hydrocarbons (HC) | A |
39-8170 | TR-SCK-H2 | 0-50% LEL, Hydrogen (H2) | A |
TR-SCR detectors | HFC / HFO / NH₃ / | For vent lines from pressure relief valves | |
39-6120-B | TR-SCR-HFC(B)-4000 | 0..4000 ppm HFC (standard R134a) | A |
39-6152 | TR-SCR-NH3-4000 | 0..4000 ppm Ammonia, max 2 W | A |
TR-EC detectors | NH3 / CO₂ / NO₂ |
| |
39-4250 | TR-EC-NH3-100 | 0 - 100 ppm | A |
39-4251 | TR-EC-NH3-1000 | 0 - 1000 ppm | A |
39-4252 | TR-EC-NH3-5000 | 0 - 5000 ppm | A |
39-4253 | TR-EC-NH3-10000 | 0 - 10000 ppm | A |
39-4260 | TR-EC-CO | 0-300 ppm | A |
39-4240 | TR-EC-NO2 | 0-20 ppm | A |
Download related material for this product:
Our G-Series refrigerant gas detectors can be delivered with sensors for the following gas types:
CO2
HFC
HFO
NH3
R290
PRODUCT NAME
Short Description
Part no.: XXXXXXX
PRODUCT NAME
Short Description
Part no.: XXXXXXX
TR-Series gas detector transmitters are robustly designed for use in harsh environments, offering simply reliable gas detection for industrial refrigerant applications.
There are a number of variants in the TR-xx platform to meet application-specific needs, all sharing a common set of
features.
These include:
• Selectable analogue output (4-20mA, 0-10V)
• Connectivity to MPU or SPU monitoring unit
• Integrate with any PLC or gas detection controller accepting analogue signals
• -40°C - + 50°C operating range (exc. TR-EC)
• Maintenance calibration gas & TR calibration kit
• Power supply 12-30V DC
TR-Series refrigerant gas detector transmitters can be delivered in several versions depending on the application and gas used.
The following options are available:
Model Types
TR-IR
CO2 detection using infrared sensor
IP67 enclosure
TR-SC
HFC / HFO / NH3 / R290 / flammable gas / VOC detection using semiconductor sensor
IP54 enclosure
TR-SCK
HFC / HFO / NH3 / R290 / flammable gas detection using semiconductor sensor
IP54 enclosure
Remote sensor, 1.5m cable
Ventilation ducts installation (plastic tube with the sensor
mounted with a rubber sleeve
directly in the channel)
TR-SCR
HFC / HFO / NH3 detector using semiconductor sensor
IP54 enclosure
Remote sensor, 1.5m cable
Vent lines from pressure relief valve installation
Pipe fitting in brass ½ ” Flare
TR-EC
NH3 / CO / NO2 detector using electrochemical sensor
IP67 enclosure
NH3: -30°C - + 50°C operating range
CO / NO2: -10°C - + 40°C operating range
TECHNICAL DATA
TR-EC-CO / TR-EC-NO2
TR-EC-CO | TR-EC-NO2 | |
Gas type: | Carbon monoxide (CO) | Nitrogen dioxide (NO2) |
Material: | Polycarbonate | Polycarbonate |
Method: | Electrochemical | Electrochemical |
Range: | 0-300 ppm | 0-20 ppm |
Lifetime sensor: | ~ 6 year | ~ 2 year |
Calibration interval: | Automatic zero adjustment, calibration span once a year. | Automatic zero adjustment, calibration span once a year. |
Power consumption: | 20mA | 20mA |
Power supply: | 12..28V DC | 12..28V DC |
Output: | 4..20mA / 0..10V DC linear | 4..20mA / 0..10V DC linear |
Ambient temp: | -10ºC..+40ºC | -10ºC..+40ºC |
Ambient humidity: | 0..90% RH | 0..90% RH |
Enclosure: | IP56 | IP56 |
Dimensions: | 80 x 82 x 86 mm | 80 x 82 x 86 mm |
Weight: | 190g | 190g |
Approvals: | CE, TÜV approved according to VDI | CE, TÜV approved according to VDI |
TR-EC-NH3
Gas type: | Ammonia (NH3) |
Material: | Polycarbonate |
Method: | Electrochemical |
Range: | 0-100 ppm / 0-1000 ppm / 0-5000 ppm / B1020-10000 ppm |
Lifetime sensor: | ~ 2-3 year |
Calibration interval: | > once a year. B101 |
Max (RL): | 250 ohm (input impedance) |
Power consumption: | 20mA |
Power supply: | 12..36V DC |
Output: | 4..20mA linear |
Ambient temp: | -30ºC..+50ºC |
Ambient humidity: | 15..90% RH |
Enclosure: | IP56 |
Dimensions: | 80 x 82 x 60 mm |
Weight: | 180g |
Approvals: | CE, EMC |
TR-SC-..
Sensor type: | Semiconductor |
Response time (T90): | <10 seconds |
Output signal: | 4..20mA (max 500 ohm) / 0..10V DC |
Calibration: | “zero / span” ≥ once per year |
Lifetime sensor: | >5 years (replacement recommended every 5th year or when unit can not be recalibrated) |
Power supply: | 12..30V DC |
Housing: | PC polycarbonate (IP54) |
Cable gland: | 1 x M16 |
TR-SC, Splash Proof (IP54) | |
Range / Gas | TR-SC-HCFC-4000: 0-4000ppm / HCFC (R22) |
TR-SC-HFC(A)-4000: 0-4000ppm / HFC (R404a, R407a, R410a, R507) | |
TR-SC-HFC(B)-4000:B144 0-4000ppm / (R134) | |
TR-SC-NH3-1000: 0-1000ppm / Ammonia | |
TR-SC-NH3-4000: 0-4000ppm / Ammonia | |
TR-SC-HC:B147 0-50% LEL / Hydrocarbon | |
TR-SC-H2:141:141 0-50% LEL / Hydrogen | |
Housing: | Polycarbonate / ABS |
Operating temperature: | -40ºC..+50ºC |
Operating humidity: | 10-90 % Rh (non condensing) |
Dimensions: | 130x82x56 mm |
TR-SCK, Duct Mounting | |
Range / Gas | TR-SCK-HCFC-4000: 0-4000ppm / HCFC (R22) |
TR-SCK-HFC(A)-4000 0-4000ppm / HFC (R404a, R407a, R410a, R507) | |
TR-SCK-HFC(B)-4000 0-4000ppm / (R134) | |
TR-SCK-NH3-1000 0-1000ppm / Ammonia | |
TR-SCK-NH3-4000 0-4000ppm / Ammonia | |
TR-SCK-HC 0-50% LEL / Hydrocarbon | |
TR-SCK-H2 0-50% LEL / Hydrogen | |
Transmitter Housing | 80 x 82 x 56 mm (IP54) |
Duct Tube | Plastic, L 350mm (PVC) |
Operating Temperature: | 0ºC..+50ºC |
Operating humidity: | 10-90 % Rh (non condensing) |
TR-SCR, For Vent Lines (Blow off pipes) | |
Range / Gas: | TR-SCR-HFC(B)-4000: 0-4000ppm / HFC (R134) |
TR-SCR-NH3-4000 0-4000ppm / Ammonia | |
Transmitter Housing | 80 x 82 x 56 mm (IP54) |
Pipe Connection: | 70x25 mm HFC - brass ½”-flare NH3 - steel R½” |
Operating Temperature: | 0ºC..+50ºC |
Operating humidity: | 10-90 % Rh (non condensing) |
TR-IR
TR-IR-CO2, Splash Proof (IP67) | |
Housing: | PC polycarbonate (IP67) |
Power Supply: | 12..30V DC |
Power consumption: | 2,5W |
Sensor type: | NDIR |
Response time (T90): | <10 seconds |
Output signal: | 4..20mA (min 250..max 500 ohm) / 0..10V DC |
Calibration: | Automatic Baseline Correction |
Control/Check: | The detector should be tested at least once per year |
Sensor Lifetime: | >15 year (replacement recommended every 10th year or when the unit no longer indicates any gas) |
Operating temperature: | -40ºC..50ºC |
Operating humidity: | 10-90 % Rh (non-condensing) |
Cable gland: | 1 x M16 |
Dimensions (LxHxD) | 80 x 82 x 56 mm |
Range / Gas: | TR-IR-CO2: 0-10000ppm Carbon Dioxide |
TR-IR-CO2: 0-20000/30000ppm Carbon Dioxide |
Coming soon...
Order Code | Model | Details | PG |
TR-IR | CO₂ |
| |
39-4312 | TR-IR-CO2-10000 | 0-10000 ppm, max 2,5 W | A |
39-4314 | TR-IR-CO2-30000 | 0-30000 ppm, max 2,5 W | A |
TR-SC detectors | HFC / HFO / NH₃ / R290 / flammable gas | ||
39-4120-A | TR-SC-HFC(A)-4000 | 0..4000 ppm HFC (standard R404a / R507) | A |
39-4120-B | TR-SC-HFC(B)-4000 | 0..4000 ppm HFC (standard R134a) | A |
39-4152 | TR-SC-NH3-4000 | 0..4000 ppm Ammonia, max 2 W | A |
39-4153 | TR-SC-NH3-10000 | 0..10000 ppm Ammonia, max 2 W | A |
39-4130 | TR-SC-HC | 0-50% LEL, General for Hydrocarbons (HC) | A |
39-4170 | TR-SC-H2 | 0-50% LEL, Hydrogen (H2) | A |
TR-SCK detectors | HFC / HFO / NH₃/ R290 / flammable gas | For ventilation ducts | |
39-8120-A | TR-SCK-HFC(A)-4000 | 0..4000 ppm HFC (standard R404a / R507) | A |
39-8120-B | TR-SCK-HFC(B)-4000 | 0..4000 ppm HFC (standard R134a) | A |
39-8152 | TR-SCK-NH3-4000 | 0..4000 ppm Ammonia, max 2 W | A |
39-8130 | TR-SCK-HC | 0-50% LEL, General for Hydrocarbons (HC) | A |
39-8170 | TR-SCK-H2 | 0-50% LEL, Hydrogen (H2) | A |
TR-SCR detectors | HFC / HFO / NH₃ / | For vent lines from pressure relief valves | |
39-6120-B | TR-SCR-HFC(B)-4000 | 0..4000 ppm HFC (standard R134a) | A |
39-6152 | TR-SCR-NH3-4000 | 0..4000 ppm Ammonia, max 2 W | A |
TR-EC detectors | NH3 / CO₂ / NO₂ |
| |
39-4250 | TR-EC-NH3-100 | 0 - 100 ppm | A |
39-4251 | TR-EC-NH3-1000 | 0 - 1000 ppm | A |
39-4252 | TR-EC-NH3-5000 | 0 - 5000 ppm | A |
39-4253 | TR-EC-NH3-10000 | 0 - 10000 ppm | A |
39-4260 | TR-EC-CO | 0-300 ppm | A |
39-4240 | TR-EC-NO2 | 0-20 ppm | A |
Download related material for this product:
Our G-Series refrigerant gas detectors can be delivered with sensors for the following gas types:
CO2
HFC
HFO
NH3
R290
PRODUCT NAME
Short Description
Part no.: XXXXXXX
PRODUCT NAME
Short Description
Part no.: XXXXXXX