AQUIS500

Water & Brine Detector

The Aquis system is developed for detection of ammonia leaks
in refrigeration systems. The development of this robust and practical system is based on many years of experience can be used for water
as well as brine.

The sensor can be used to measure ammonia (NH₃) in water. In an
aqueous solution, ammonia is in a pH-dependent equilibrium with the ammonium ion (NH4+ ions). Since the NH4+ ions are converted to
ammonia when adding lye, the sensor can detect ammonia.
(the NH4+ ions are not detected)

The ammonia sensor consists of a pH glass electrode and a reference electrode. Both electrodes are positioned in an electrolyte. The electrolyte is separated from the test medium with a hydrophobic, gas permeable membrane.

The local change in pH value is measured at the high resistance of the integrated pH electrode.

The monitoring unit provides a 4..20mA output, which can be connected to an external PLC.

Different sensor can be connected to the Aquis500 depending on the application and pressure in the system. The sensors can be quickly and easily installed.

TECHNICAL DATA:

Designed for monitoring of ammonia in secondary cooling systems

Detection in Water, Brine mixtures, e.g. Ethylene, Tyfoxit, Hycool, etc

Selectable display of: numbers, graph or trends

Measuring low concentration (<0.2 ppm)

Measuring range: 0.01..9999 ppm

Output: 4..20mA, relay SPDT

Power supply: 230V AC

Pressure range: (0) 1 ... 6 bar

Easy installation and easy to use

User-friendly programming and access
to plant documentation

Languages: English, French, German

Complies with EN 378 regulations

Expected sensor lifetime ≈ 2 year

Sensors are a consumable part.

Maintenance: every 6 months at
normal operation

Temperature range media (in circuit): depending on sensor type. IP67

NOTE: When ordering, brine type must be specified!

Order Code Model Details PG
35-210 Aquis 500 Monitoring unit, wall mount Net
35-220 NH3 sensor, standard Media temp (0..+50°C). Net
35-221 NH3 sensor, low temp Media temp (-8..+30°C). Net
35-229 Coax cable set 1x5mm 75Ω, 5,0m Net
35-230 Pipe fitting for sensor Retractable pipe fitting with built in pressure reducer, max 6 bar. Net
Pipe/process connection (G 1¼”)
Built in shut of valve for sensor maintenance.
35-231 Aquis bottle kit Mounting kit with hose and bottle for liquid sample. Net

The Aquis system is developed for detection of ammonia leaks
in refrigeration systems. The development of this robust and practical system is based on many years of experience can be used for water
as well as brine.

The sensor can be used to measure ammonia (NH₃) in water. In an
aqueous solution, ammonia is in a pH-dependent equilibrium with the ammonium ion (NH4+ ions). Since the NH4+ ions are converted to
ammonia when adding lye, the sensor can detect ammonia.
(the NH4+ ions are not detected)

The ammonia sensor consists of a pH glass electrode and a reference electrode. Both electrodes are positioned in an electrolyte. The electrolyte is separated from the test medium with a hydrophobic, gas permeable membrane.

The local change in pH value is measured at the high resistance of the integrated pH electrode.

The monitoring unit provides a 4..20mA output, which can be connected to an external PLC.

Different sensor can be connected to the Aquis500 depending on the application and pressure in the system. The sensors can be quickly and easily installed.

TECHNICAL DATA:

Designed for monitoring of ammonia in secondary cooling systems

Detection in Water, Brine mixtures, e.g. Ethylene, Tyfoxit, Hycool, etc

Selectable display of: numbers, graph or trends

Measuring low concentration (<0.2 ppm)

Measuring range: 0.01..9999 ppm

Output: 4..20mA, relay SPDT

Power supply: 230V AC

Pressure range: (0) 1 ... 6 bar

Easy installation and easy to use

User-friendly programming and access
to plant documentation

Languages: English, French, German

Complies with EN 378 regulations

Expected sensor lifetime ≈ 2 year

Sensors are a consumable part.

Maintenance: every 6 months at
normal operation

Temperature range media (in circuit): depending on sensor type. IP67

NOTE: When ordering, brine type must be specified!

Order Code Model Details PG
35-210 Aquis 500 Monitoring unit, wall mount Net
35-220 NH3 sensor, standard Media temp (0..+50°C). Net
35-221 NH3 sensor, low temp Media temp (-8..+30°C). Net
35-229 Coax cable set 1x5mm 75Ω, 5,0m Net
35-230 Pipe fitting for sensor Retractable pipe fitting with built in pressure reducer, max 6 bar. Net
Pipe/process connection (G 1¼”)
Built in shut of valve for sensor maintenance.
35-231 Aquis bottle kit Mounting kit with hose and bottle for liquid sample. Net